J-HH
Application Area
Cable Construction
Inner Conductor
Electrolytic Copper Wire
EN, IEC 60228
Insulation
HFFR, DIN VDE 0815 Suitable for isolated color
70°C, EN 50290-2-26
Stranding
Twisted in group
Outer sheath
HFFR, RAL 3000 Red,
EN 50290-2-27
Technicial Properties
Operating Temperature -30°C … + 70°C
Min. Bending Radius 10 x D
Operating Voltage 300 V
Insulation Resistance 100 MΩ km
Max. Capacitance 100 nF/km
Max. Capacitance Unbalance 300 pF / 500m
Test Voltage  
< 1.00 mm 800V
≥ 1.00 mm 1000V
Packing 500 / 1000 m

Standards
TSE K 173
Euro Class
Eca
Flame Retardancy Test
EN 60332-1-2
Smoke Density Test
EN 61034-2
Corrosive Gas Test
EN 60754-2
Conductor Cross Section
(mm) - (mm²)
Conductor Resistance max.
(Ohm/km @ 20 °C)
 0.60 mm 130 Ω/km
 0.80 mm 73.20 Ω/km
 1.00 mm 44.40 Ω/km
  1.00 mm² 36.20 Ω/km
  1.50 mm² 24.20 Ω/km
  2.50 mm² 14.80 Ω/km

 

No. Of Cores x Cross Section
(mm) - (mm²)
Overall Diameter
(mm)
Copper Weight
(kg/km)
Cable Weight
(kg/km)
1 x 2 x 0.60 4.9 7.0 28
2 x 2 x 0.60 5.3 13.0 48
3 x 2 x 0.60 6.1 18.0 51
4 x 2 x 0.60 6.6 23.0 59
5 x 2 x 0.60 7.3 32.0 82
6 x 2 x 0.60 7.8 46.0 93
10 x 2 x 0.60 8.8 56.0 111
       
1 x 2 x 0.80 5.9 13.0 39
2 x 2 x 0.80 6.8 22.0 59
3 x 2 x 0.80 5.3 32.0 79
4 x 2 x 0.80 8.8 42.0 99
5 x 2 x 0.80 10.3 62.0 139
6 x 2 x 0.80 11.0 82.0 169
10 x 2 x 0.80 12.8 102.0 219
       
1 x 2 x 1.00 6.8 16.0 43
2 x 2 x 1.00 8.4 30.0 61
3 x 2 x 1.00 10.0 45.0 119
4 x 2 x 1.00 11.2 62.0 193
6 x 2 x 1.00 13.0 90.0 193
8 x 2 x 1.00 14.6 120.0 247
10 x 2 x 1.00 16.0 148.0 304
       
1 x 2 x 1.50 7.8 30.0 63
2 x 2 x 1.50 9.2 55.0 111
3 x 2 x 1.50 12.0 80.0 168
4 x 2 x 1.50 13.4 108 208
6 x 2 x 1.50 16.0 160.0 303
8 x 2 x 1.50 18.2 212.0 399
10 x 2 x 1.50 19.5 264.0 477