Data Sheet İndir
EC400 Cat 6 U/UTP Duplex
Application Area
10Base-T, 100Base-T, 1000Base-T, and Fieldbus systems. Applicable for Power over Ethernet (PoE) / PoE+
Cable Construction
• 23 AWG Bare Copper 
• PE Insulation
• Pair Seperator
• Ø 6.20 x 14.20mm ± 0.20 LSZH Jacket
Standards
EIA/TIA-568
ISO/IEC 11801 Class E
IEC 61156-5 , EN 50173-1
EN 50288-6-1
Technical Properties
Copper Weight 38.2 kg/km
Min. Bending radius    during draw in 50 mm
Min. Bending radius    permanently installed 25 mm
Max. Tensile Strength 90 N
Min. Crush Resistance 1000 N/10 cm
Min. Impact 10 Impacts
Installation Temperature 0°C … + 50°C
Operating Temperature -20°C … + 70°C
Packing 305 / 500 m
Electrical Properties                                       at 20ºC
Max. Conductor Resistance < 9.5 Ω / km
Max. Resistance Unbalance < 2%
Min. Insulation Resistance 5000 MΩ x m
Mutual Capacitance < 60 pF / m
Max. Capacitance Unbalance 1600 pF / km
Impedance at 100 MHz 100 ± 5 Ω
Velocity of Propagation 66 %
Delay Skew < 45 ns / 100 m
Test Voltage 1000 V
Operating Voltage 125 V
Product Name Euro Class Cable Weight Flame Retardancy Corrosive Gases  Smoke Density Download
Data Sheet
EC400 Duplex CAT 6 U/UTP LSZH Eca Eca 92 Kg/Km EN 60332-1-2 EN 50267-2-3 EN 61034-2  Download
EC400 Duplex CAT 6 U/UTP LSZH Dca Dca 92 Kg/Km EN 60332-1-2 EN 50267-2-3 EN 61034-2  Download
Frequency 
(MHz)
Attenuation 
(dB/100 m)
NEXT
(dB)
PS - NEXT
(dB)
ACR
(dB/100 m)
PS-ACR
(dB/100 m)
ACRF
(dB/100 m)
PS-ACRF
(dB/100 m)
Return Loss
(dB)
1 2.0 83 80 85 82 83 80 25
4 3.6 73 70 70 67 70 67 31
10 6.0 73 70 65 62 60 57 30
100 19.5 55 52 40 37 35 32 25
200 28.5 50 47 25 22 30 27 22
250 32.0 45 42 25 22 22 19 22
300 33.0 40 37 15 12 20 17 22
400 39.0 40 37 7 4 20 17 20