JE-H(St)H ...Bd FE 180 PH 120
Application Area
These cables are used as fire alarm cables in electronic fire control systems in fixed installations. They provide continuity of performance during fire (Circuit integrity for 180 minutes and circuit integrity with mechanical shock for 120 minutes). These cables with a static screen must protect against electromagnetic interference from the environment. It is used halogen free in the cable structure and it is used in places where people are concentrated in places where they should not be affected by fire conditions since they do not transmit and relay the flame late and do not generate toxic gas after burning and do not generate black smoke which prevents vision.
Cable Construction
Inner Conductor
Electrolytic Copper Wire,
Class 1 IEC 60228
Insulation
Silicon compoaunt, cross-linked insulation,
Core identification acc. to DIN VDE 0815
EN 50363-5 EI8
Stranding
Twisted in group
Polyester
Pet Band 100% Coverage
Fibre Glass Tape 100% Coverage
Drain Wire
Tinned Copper Drain Wire
Foil
Al-Pet Foil 100% Coverage
Outer sheath
HFFR, RAL 2004 Orange 70°C
EN 50290-2-27
Standards
Operating Temperature -30°C … + 70°C
Min. Bending Radius 10 x D
Operating Voltage 300 V
Insulation Resistance 100 MΩ km
Test Voltage                       
0.6 ve 0.8 mm 800 V
> 1.0 mm 1000 V
Packing 500 / 1000 m

Standards
TSE K 173, DIN VDE 0815
Flame Retardancy Test
EN 60332-1-2
Smoke Density Test
EN 61034-2
Corrosive Gas Test
TS EN 60754-2
Current Continuity Testi
IEC 60331-21 FE180
Circuit Integrity Testi
EN 50200 PH120
Conductor Cross Section
(mm²)
Conductor Resistance max.
(Ohm/km @ 20 °C)
0.60 mm 130 Ω/km
0.80 mm  73.20  Ω/km
1.00 mm  44.40  Ω/km
 1.00 mm²  36.20  Ω/km
 1.50 mm²  24.20  Ω/km
 2.50 mm²  14.80  Ω/km
No. Of Cores x Cross Section
(mm²)
Overall Diameter
(mm)
Copper Weight
(kg/km)
Cable Weight
(kg/km)
1 x 2 x 0.60 4.4 8.0 24
2 x 2 x 0.60 5.1 14.0 34
3 x 2 x 0.60 6.1 17.0 46
4 x 2 x 0.60 6.5 23.0 55
8 x 2 x 0.60 7.9 45.0 89
12 x 2 x 0.60 9.4 68.0 126
       
1 x 2 x 0.80 5.6 11.0 37
2 x 2 x 0.80 6.7 21.0 56
3 x 2 x 0.80 8.2 30.0 78
4 x 2 x 0.80 9.0 40.0 96
8 x 2 x 0.80 11.2 78.0 163
12 x 2 x 0.80 13.8 119.0 244
       
1 x 2 x 1.00 6.2 19.0 55
2 x 2 x 1.00 8.1 33.0 85
4 x 2 x 1.00 10.6 78.0 164
       
1 x 2 x 1.50 6.8 32.0 70
2 x 2 x 1.50 9.6 57.0 125
4 x 2 x 1.50 11.3 111.0 198
       
1 x 2 x 2.50 7.8 49.0 97
2 x 2 x 2.50 10.6 100.0 167
4 x 2 x 2.50 14.1 182.6 313